The compartment fire test was conducted on the 9.1 m x 6.1 m steel-concrete composite floor, located in the south-central bay of the two-story steel gravity frame two bays by three bays in plan. The test floor assembly was designed and constructed to achieve a 2-hour fire-resistance rating per American Society for Testing and Materials (ASTM) standard E119. The fire-exposed composite slab was reinforced with the steel wire mesh mat (60 mm2/m) equivalent to the minimum code-prescribed steel reinforcement for shrinkage and temperature crack control under normal conditions. The fire exposure condition was created using natural gas burners to mimic a standard temperature-time relationship in the upper layer of the test compartment. During fire exposure, the heated floor assembly was subjected to a mechanical load of 2.7 kPa, determined from the gravity load combination for extraordinary events as permitted by the applicable building code. This is the dataset from the first (Test #1) of four compartment fire tests conducted as part of the research project "Measurement of Structural Performance in Fire: Steel-Concrete Composite Floor Systems Subject to Fire Phase 2" under the National Institute of Standards and Technology (NIST) Engineering Laboratory's Fire Risk Reduction in Buildings Program.
About this Dataset
| Title | Data from Fire Resilience of a Steel-Concrete Composite Floor System: Full-Scale Experimental Evaluation for Influence of Slab Reinforcement (Test #1) |
|---|---|
| Description | The compartment fire test was conducted on the 9.1 m x 6.1 m steel-concrete composite floor, located in the south-central bay of the two-story steel gravity frame two bays by three bays in plan. The test floor assembly was designed and constructed to achieve a 2-hour fire-resistance rating per American Society for Testing and Materials (ASTM) standard E119. The fire-exposed composite slab was reinforced with the steel wire mesh mat (60 mm2/m) equivalent to the minimum code-prescribed steel reinforcement for shrinkage and temperature crack control under normal conditions. The fire exposure condition was created using natural gas burners to mimic a standard temperature-time relationship in the upper layer of the test compartment. During fire exposure, the heated floor assembly was subjected to a mechanical load of 2.7 kPa, determined from the gravity load combination for extraordinary events as permitted by the applicable building code. This is the dataset from the first (Test #1) of four compartment fire tests conducted as part of the research project "Measurement of Structural Performance in Fire: Steel-Concrete Composite Floor Systems Subject to Fire Phase 2" under the National Institute of Standards and Technology (NIST) Engineering Laboratory's Fire Risk Reduction in Buildings Program. |
| Modified | 2021-10-04 00:00:00 |
| Publisher Name | National Institute of Standards and Technology |
| Contact | mailto:[email protected] |
| Keywords | fire , composite floor , steel beam , shear connection , steel building , fire resistance , passive fire protection |
{
"identifier": "ark:\/88434\/mds2-2484",
"accessLevel": "public",
"contactPoint": {
"hasEmail": "mailto:[email protected]",
"fn": "Selvarajah Ramesh"
},
"programCode": [
"006:045"
],
"landingPage": "https:\/\/data.nist.gov\/od\/id\/mds2-2484",
"title": "Data from Fire Resilience of a Steel-Concrete Composite Floor System: Full-Scale Experimental Evaluation for Influence of Slab Reinforcement (Test #1)",
"description": "The compartment fire test was conducted on the 9.1 m x 6.1 m steel-concrete composite floor, located in the south-central bay of the two-story steel gravity frame two bays by three bays in plan. The test floor assembly was designed and constructed to achieve a 2-hour fire-resistance rating per American Society for Testing and Materials (ASTM) standard E119. The fire-exposed composite slab was reinforced with the steel wire mesh mat (60 mm2\/m) equivalent to the minimum code-prescribed steel reinforcement for shrinkage and temperature crack control under normal conditions. The fire exposure condition was created using natural gas burners to mimic a standard temperature-time relationship in the upper layer of the test compartment. During fire exposure, the heated floor assembly was subjected to a mechanical load of 2.7 kPa, determined from the gravity load combination for extraordinary events as permitted by the applicable building code. This is the dataset from the first (Test #1) of four compartment fire tests conducted as part of the research project \"Measurement of Structural Performance in Fire: Steel-Concrete Composite Floor Systems Subject to Fire Phase 2\" under the National Institute of Standards and Technology (NIST) Engineering Laboratory's Fire Risk Reduction in Buildings Program.",
"language": [
"en"
],
"distribution": [
{
"downloadURL": "https:\/\/data.nist.gov\/od\/ds\/mds2-2484\/NFRL_CompositeFloorTest_No1.zip.sha256",
"mediaType": "text\/plain",
"title": "SHA256 File for NFRL Composite Floor Test Phase 2 Test #1"
},
{
"downloadURL": "https:\/\/data.nist.gov\/od\/ds\/mds2-2484\/NFRL_CompositeFloorTest_No1.zip",
"description": "This is the dataset from the first (Test #1) of four compartment fire tests conducted as part of the project ?Measurement of Structural Performance in Fire: Steel-Concrete Composite Floor Systems Subject to Fire ? Phase 2? under the National Institute of Standards and Technology (NIST) Engineering Laboratory?s Fire Risk Reduction in Buildings Program.",
"mediaType": "application\/x-zip-compressed",
"title": "NFRL Composite Floor Test Phase 2 Test #1"
},
{
"accessURL": "https:\/\/doi.org\/10.18434\/mds2-2484",
"title": "DOI Access for Fire Resilience of a Steel-Concrete Composite Floor System: Full-Scale Experimental Evaluation for U.S. Prescriptive Approach with a 2-Hour Fire-Resistance Rating (Test #1)"
}
],
"bureauCode": [
"006:55"
],
"modified": "2021-10-04 00:00:00",
"publisher": {
"@type": "org:Organization",
"name": "National Institute of Standards and Technology"
},
"theme": [
"Fire:Structural fire resistance"
],
"keyword": [
"fire",
"composite floor",
"steel beam",
"shear connection",
"steel building",
"fire resistance",
"passive fire protection"
]
}